8. Other Control
8.1
Backup Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor unit
from operating, and then conduct emergency operation only with operational compressors or
outdoor units.
"Emergency operation with remote controller reset" and "Emergency operation with outdoor unit
PCB setting" are available.
(1) Emergency operation with remote controller reset
[Operating method]
Reset the remote controller. (Press the
button for 4 seconds or more.)
[Details of operation]
Disable the defective outdoor unit from operating temporarily, and then only operate other
outdoor units.
(On the system with 1 outdoor unit, this emergency operation is not available.)
(2) Emergency operation with outdoor unit PCB setting
[Setting method]
Make setting of the unit, "the operation of which is to be disabled", in field setting mode
(setting mode 2).
[Details of operation]
Disable the defective outdoor unit from operating, and then only operate other outdoor units.
(On the system with 1 outdoor unit, this emergency operation is not available.)
8.2
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control forcibly
by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor for outdoor unit is required.
Refer to page 128 for the power consumption limitation details.
Operating method
Applicable model
(1) Emergency operation with
remote controller reset
(Auto backup operation)
(2) Emergency operation with
outdoor unit PCB setting
(Manual backup operation)
RXLQ144-240TATJU
RXLQ144-240TAYDU
RXLQ144-240TAYCU
RXYQ192-384TAYCU
Backup operation by outdoor
unit
Backup operation by outdoor
unit
ON/OFF
Setting item
Content
Demand 1
The compressor operates at the power of 60-95% or less of the rating.
Demand 2
The compressor operates at the power of 40-55% or less of the rating.
Demand 3
Forced thermostat OFF
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...