Troubleshooting by Error Code
SiUS341802E
279
Service Diagnosis
Check
the
transmission
wiring between
centralized control
equipment for any broken
wire.
Is the
voltage
between the
terminals F1 (+) and F2 (-)
in the range of 15.2
to 17.6 VDC?
Check the
transmission
wiring between main
centralized control
equipment for any
broken wire.
Replace the centralized
control equipment.
Centralized control
equipment: Normal
OK
Correct the wiring.
NG
A
NO
Correct the wiring.
NG
YES
YES
Disconnect the transmission
wiring of the main centralized
control equipment, and then
check the voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multimeter.
It is supposed that the error
results from external factors
(e.g. noises) from other
equipment.
CHECK 15
CHECK 15
Has
the main
centralized control
equipment setting connector
been connected?
OK
Correct the connection of the
connector.
NO
CHECK 15