Troubleshooting by Error Code
SiUS341802E
275
Service Diagnosis
YES
YES
NO
Make setting again, and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P).
NO
Correct the multi combination of
outdoor units.
Diagnosis Flowchart-6
Is the multi
combination of
outdoor units
proper?
NO
Was the
outdoor unit PCB
replaced with a spare
PCB?
Replace the outdoor unit main PCB
(A1P).
YES
YES
YES
YES
NO
Is the
procurement of the
spare PCB proper?
Procure a proper spare PCB.
Is the setting of the
spare PCB proper?
Error code
Sub code
UA-35
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...