Outline of Control (Indoor Unit)
Functions and Control
74
9.4.2 With Optional Infrared Presence/Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
· Cooling operation
· Heating operation
Dry operation
· When Tro
≤
24.5°C (76.1°F)
· When Tro > 24.5°C (76.1°F)
∗
: Description of symbols
∆
T : Room temperature or temperature around people – Remote controller set temperature
Tro : Room temperature or temperature around people at the start of dry operation
Tr : Room temperature or temperature around people
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may cause
the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of
the temperature around people.
•
Heating operation
· When the floor temperature is higher than suction air temperature (R1T), R1T will be treated
as the control target temperature in operation.
· When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the
control temperature for operation.
•
Cooling operation
· When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as
the control target temperature for operation.
· When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the
control temperature for operation.
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≤
–1.0˚C (–1.8˚F)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
Thermostat OFF
Normal operation
(Thermostat ON)
∆
T
≥ +
1.0˚C (
+
1.8˚F)
∆
T
≤
–1.0˚C (–1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0˚C (– 1.8˚F)
Tr > Tro + 1.0˚C (+ 1.8˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5˚C (– 2.7˚F)
Tr > Tro + 0.5˚C (+ 0.9˚F)
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...