Field Setting from Outdoor Unit
SiUS341802E
119
Field Settings and Test Operation
Accessing modes
BS1 is used to change the mode you want to access.
• Access mode 1
Press BS1 once. Segment indication changes to:
• Access mode 2
Press BS1 for at least 5 seconds. Segment indication changes to:
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the unit.
•
Changing and access the setting in mode 1:
Once mode1 is selected (press BS1 once), you can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
Example:
Checking the content of parameter [1-10] (to know how many indoor units are connected to the system).
Mode: 1
Setting: 10
•
Make sure the segment indication is as during normal operation (default situation when shipped from factory).
•
Press BS1 once; result segment display:
•
Press BS2 10 times; result segment display:
•
Press BS3 1 time; the value which is returned (depending on the actual field situation), is the amount of
indoor units which are connected to the system.
Result: mode1 setting 10 is addressed and selected, return value is monitored information
•
To leave the monitoring function, press BS1 once, you will return to the default situation when shipped from
factory.
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
•
Changing and access the setting in mode 2:
Once mode 2 is selected (press BS1 for more than 5 seconds), you can select the wanted setting. It is done
by pressing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
•
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (press BS1 for more than 5 seconds) you can select the wanted setting. It is done
by pressing BS2.
- Accessing the selected setting's value is done by pressing BS3 once.
- Now BS2 is used to select the required value of the selected setting.
- When the required value is selected, you can define the change of value by pressing BS3 once.
- Press BS3 again to start operation according to the chosen value.
INFORMATION If you get confused in the middle of the process, press BS1.
Then it returns to idle situation (no indication on segment displays: blank)
Result: mode 1 is accessed.
Result: mode 1 setting 10 is addressed.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...