Troubleshooting by Error Code
SiUS341802E
211
Service Diagnosis
2.31 Inverter Compressor Motor Lock
Error Code
E5
Applicable
Models
All outdoor unit models
Method of Error
Detection
Outdoor unit PCB takes the position signal from UVW line connected between the inverter and
compressor, and the error is detected when any abnormality is observed in the phase-current
waveform.
Error Decision
Conditions
This error will be output when the inverter compressor motor does not start up even in forced
startup mode.
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5 MPa (72.5 psi) or more)
UVW connection error
Defective inverter PCB
Stop valve is not opened
Troubleshooting
Make proper wire connections.
Make proper wire connections.
NO
NO
NO
NO
YES
YES
YES
YES
Go to the next page.
Power OFF
Is the
connection
line of the
compressor
normal?
Are wire
connections
made to phases U,
V and W in the proper
order and
manner?
Are wire
connections
made according to the
Wiring Diagram?
U
V
W
Is the stop
valve open?
Replace the connection line,
and then securely connect the
connector.
Field factor
Open the stop valve.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check the compressor
cable for disconnection
and flaws.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...