Troubleshooting by Error Code
SiUS341802E
205
Service Diagnosis
2.26 Outdoor Unit PCB Abnormality
Error Code
E1
Applicable
Models
All outdoor unit models
Method of Error
Detection
Abnormality is detected under the communication conditions in the hardware section between the
indoor unit and outdoor unit.
Error Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal
Supposed
Causes
Defective outdoor unit main PCB (A1P)
Defective connection communication line between indoor and outdoor units
Troubleshooting
Return to normal?
YES
External factor other than
error (for example, noise
etc.).
Connect the communication
line correctly.
Replace the outdoor unit
main PCB (A1P).
NO
NO
Check if
inside / outside
relay wires of outdoor
unit main PCB is
disconnected.
YES
Turn OFF the power once and
turn ON again.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series