Troubleshooting by Error Code
SiUS341802E
267
Service Diagnosis
YES
NO
YES
NO
The
multi transmission
wirings to multi slave 2
have caused wiring disconnection in
them or are being
disconnected.
Replace the outdoor unit main
PCB (A1P) for multi slave 2.
Disconnect the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P).
YES
NO
The
multi transmission
wirings to multi slave 1 have
caused wiring disconnection in
them or are being
disconnected.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P) for multi slave 1.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Diagnosis Flowchart-3
(Transmission error between master
and slave 1)
Error code
Sub code
U7-03
Diagnosis Flowchart-4
(Transmission error between master
and slave 2)
Error code
Sub code
U7-04
Diagnosis Flowchart-5
(Multi system error)
Error code
Sub code
U7-05
Multi outdoor unit
system?