Troubleshooting by Error Code
SiUS341802E
265
Service Diagnosis
NO
NO
YES
YES
NO
YES
YES
Connect the power supply cable
of the external control adaptor
for outdoor unit to the 16 VDC
power supply line.
Replace the outdoor unit main
PCB (A1P).
Replace the external control
adaptor PCB.
Replace the outdoor unit
main PCB (A1P).
NO
NO
YES
Modify the transmission wirings
to the external control adaptor for
outdoor unit.
Diagnosis Flowchart-1
Supply power to the outdoor
unit.
Is power supplied to
the outdoor unit?
Is the
normal
operation monitor LED
on the outdoor unit
main PCB
blinking?
Is the
normal
operation monitor LED
on the external control
adaptor for outdoor
unit blinking?
(Transmission error when the
external control adaptor is mounted)
Is the
power
supply cable of the
external control adaptor
for outdoor unit connected
to the 16 VDC
power supply
line?
Is
there any
wiring
disconnection or wiring
error in the transmission
wirings to the external
control adaptor for
outdoor unit?
Error code
Sub code
U7-01