PJ - 04
Incorrect type of inverter PCB (Master)
Refer to the
PJ
flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
PJ - 05
Incorrect type of inverter PCB (Slave 1)
PJ - 06
Incorrect type of inverter PCB (Slave 2)
PJ - 09
Incorrect type of fan PCB (Master): M1F
PJ - 10
Incorrect type of fan PCB (Master): M2F
PJ - 15
Incorrect type of fan PCB (Slave 1): M1F
PJ - 16
Incorrect type of fan PCB (Slave 2): M1F
PJ - 17
Incorrect type of fan PCB (Slave 1): M2F
PJ - 18
Incorrect type of fan PCB (Slave 2): M2F
U0 - 05
Refrigerant shortage warning (cooling)
Refer to the
U0
flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
U0 - 06
Refrigerant shortage warning (heating)
U1 - 01
Reverse phase/open phase of power supply
(Master)
Refer to the
U1
flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
U1 - 04
Reverse phase/open phase of power supply
(when power ON) (Master)
U1 - 05
Reverse phase/open phase of power supply
(Slave 1)
U1 - 06
Reverse phase/open phase of power supply
(when power ON) (Slave 1)
U1 - 07
Reverse phase/open phase of power supply
(Slave 2)
U1 - 08
Reverse phase/open phase of power supply
(when power ON) (Slave 2)
U2 - 01
Shortage of inverter 1 power supply voltage
(Master)
Make a diagnosis of the relevant unit based on the following.
Shortage of power supply voltage
If the other units detect shortage of power supply voltage, power
supply voltage during operation may be unstable. Check the
power supply condition.
If a particular unit detects the error, operation of 52C may be
defective. Follow the
U2
flowchart.
Open phase of power supply
The wiring between power supply and inverter PCB may be
disconnected. Check that power supply is connected to terminal
block, terminal block is connected to PCB without broken wire or
disconnection, and reactor wiring is secured. If no abnormality is
found, follow the
U2
flowchart.
Defective capacitor in main circuit
P-N on the inverter PCB (electrolytic capacitor, power module)
may be damaged and short circuited. Operation of current limiting
relay may be defective or the wiring between the reactor and PCB
may be disconnected. Measure the resistance between P-N on
the inverter PCB and check for short circuit. If no abnormality is
found, follow the
U2
flowchart.
U2 - 02
Open phase of inverter 1 power supply (Master)
U2 - 03
Defective capacitor in inverter 1 main circuit
(Master)
U2 - 08
Shortage of inverter 1 power supply voltage
(Slave 1)
U2 - 09
Open phase of inverter 1 power supply (Slave 1)
U2 - 10
Defective capacitor in inverter 1 main circuit
(Slave 1)
U2 - 11
Shortage of inverter 1 power supply voltage
(Slave 2)
U2 - 12
Open phase of inverter 1 power supply (Slave 2)
U2 - 13
Defective capacitor in inverter 1 main circuit
(Slave 2)
U2 - 36
Fan motor 1 undervoltage (Master)
U2 - 37
Fan motor 1 undervoltage (Slave 1)
U2 - 38
Fan motor 1 undervoltage (Slave 2)
U3 - 02
Initial installation warning
Refer to the
U3
flowchart of each manual and make a diagnosis
of the relevant unit based on the Error code shown to the left.
U3 - 03
Test operation not conducted
U3 - 04
Abnormal end of test operation
U3 - 05
Premature end of test operation during initial
transmission error
U3 - 06
Premature end of test operation during normal
transmission error
U3 - 07
Premature end of test operation due to
transmission error of either unit
U3 - 08
Premature end of test operation due to
transmission error of all units
Error code
Troubleshooting
Description of error
Description of diagnosis
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...