Service Mode
SiUS341802E
39
Remote Controller
∗
1. (For FXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed is changed by
controls or external factors, the airflow rate set with the remote controller may differ from the fan tap display.
∗
2. (For FXTQ-TA models)
0 rpm
is displayed even if the fan is rotating.
∗
3. (For FXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB is
not displayed. The ON/OFF status of the humidifier connected to the wiring adaptor is displayed.
Indoor Unit Status
FLOAT
Float switch OPEN/CLOSE
T1/T2
T1/T2 input from outside OPEN/CLOSE
Th1
Suction air thermistor
Th2
Heat exchanger liquid pipe thermistor
Th3
Heat exchanger gas pipe thermistor
Th4
Discharge air thermistor
Th5
—
Th6
—
Outdoor Unit Status
Unit No.
Select the unit number you want to check.
FAN step
Fan tap
COMP
Compressor power supply frequency (Hz)
EV1
Degree that electronic expansion valve is open (pulse)
SV1
Solenoid valve ON/OFF
Th1
—
Th2
—
Th3
—
Th4
—
Th5
—
Th6
—
Forced Defrost
Forced defrost ON
Enables the forced defrost operation.
Forced defrost OFF
Disables the forced defrost operation.
Error Display
Display Error ON
Displays the error on the screen.
Display Error OFF
Displays neither errors nor warnings.
Display Warning ON
Displays a warning on the screen if an error occurs.
Display Warning OFF
No warning is displayed.
Swap Unit No.
Current Unit No.
A unit number can be transferred to another.
Transfer Unit No.
Addressed Sensor
Value
Unit No.: 0 - 15
Select the unit number you want to check.
Code
00
:
01
:
02
:
03
:
04
:
05
:
06
:
07
:
08
:
09
:
10 and over:
Remote controller thermistor (°F)
Suction air thermistor (°F)
Heat exchanger liquid pipe thermistor (°F)
Heat exchanger gas pipe thermistor (°F)
Indoor unit address No.
Outdoor unit address No.
Branch selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Differs depending on the connected indoor/outdoor unit.
Data
The corresponding data will be displayed, based on the unit
number and code selected.
Maintenance Menu
Item 2
Remarks
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...