Field Setting from Outdoor Unit
SiUS341802E
135
Field Settings and Test Operation
[2-97]: Auxiliary heater maximum allowable temperature
Auxiliary heater is allowed to energize when the outdoor air temperature is smaller than the auxiliary
heater maximum allowable temperature.
[2-98]: Auxiliary heater maximum allowable temperature release differential
Auxiliary heater is not allowed to energize when the outdoor air temperature is recovered by differential
above the auxiliary heater maximum allowable temperature.
Value
[2-97]
Auxiliary heater maximum allowable
temperature
0
–17.7°C (0°F)
1
–15°C (5°F)
2
–12.2°C (10°F)
3
–9.4°C (15°F)
4
–6.6°C (20°F)
5
–3.8°C (25°F)
6
–1.1°C (30°F)
7 (default)
1.6°C (35°F)
8
4.4°C (40°F)
9
7.2°C (45°F)
10
10°C (50°F)
11
12.7°C (55°F)
12
15.5°C (60°F)
13
18.3°C (65°F)
14
Auxiliary heater always not allowed
15
Auxiliary heater always allowed
Value
[2-98]
Auxiliary heater maximum allowable
temperature release differential
0
2.8°C (5°F)
1 (default)
5.6°C (10°F)
2
8.3°C (15°F)