SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
246
Note:
∗
1. Connect and disconnect the connector once to ensure that it is securely connected.
Replace all of the inverter PCB
(
∗
2)
,
fan
PCBs (
∗
3)
, and noise filter PCBs
(
∗
4)
.
YES
This is not the LC error.
Recheck the error code.
NO
YES
The
microcomputer
normal monitor indication
lamp (green) on the outdoor
unit main PCB (A1P)
is blinking.
Replace the inverter PCB (
∗
2).
NO
NO
YES
The
microcomputer
normal monitor indication
lamp (green) on the outdoor
unit main PCB (A1P)
is blinking.
Properly connect the connector.
NO
YES
Is the
connector
between the outdoor
unit main PCB and the sub
PCB securely
connected?
Properly connect the connector X9A
(X10A) on the sub PCB option.
NO
Is the
normal operation
indication LED on the sub
PCB blinking?
YES
NO
Replace the outdoor unit main PCB
(A1P).
YES
The fuse of
the noise filter PCB has
blown out.
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
The
LC
error recurs.
A
Model
Inverter PCB (
∗
2)
Fan PCB (
∗
3)
Noise filter PCB (
∗
4)
RXLQ-TATJU
A3P
M1F: A4P
M2F: A5P
A2P
RXLQ-TAYDU
A3P
M1F: A4P
M2F: A5P
A2P
RXLQ-TAYCU
A4P
M1F: A6P
M2F: A5P
A2P, A3P
RXYQ-TAYCU
A4P
M1F: A6P
M2F: A5P
A2P, A3P
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...