11-18
ASCII Command Interface
BE1-951
SL-GROUP Command
Purpose:
Read/Set logic for setting group module.
Syntax:
SL-GROUP[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Setting Groups
SL-N Command
Purpose:
Read, set, or copy the name of the custom logic.
Syntax:
SL-N[=<name>]
Reference:
Section 7,
BESTlogic Programmable Logic, Logic Schemes
SL-VO Command
Purpose:
Read/Set output logic.
Syntax:
SL-VO<x>[=<Boolean equation>]
Reference:
Section 7,
BESTlogic Programmable Logic, Working With Programmable Logic
User Programmable Name Setting Command
SN Command
Purpose:
Read/Set user programmable names.
Syntax:
SN[-<var>[=<name>,<TRUE label>,<FALSE label>]
Reference:
Section 7,
BESTlogic Programmable Logic, User Input and Output Logic Variable Names
Protection Setting Commands
S<g> Command
Purpose:
Read all protection settings.
Syntax:
S<g>
Reference:
Section 11,
ASCII Command Interface, Using ASCII Commands
S<g>-24 Command
Purpose:
Read/Set 24 pickup level, time delay and reset delay
Syntax:
S<g>-24[=<Pickup>,<Time Delay>,<Reset Time Delay>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-25 Command
Purpose:
Read/Set 25 delta volts, phase angle, slip freq and mode
Syntax:
S<g>-25[=<Volts>,<Ang>,<Slip>,<mode>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-25VM Command
Purpose:
Read/Set 25VM live volts, dead volts, time delay, and VM1 & VM2 logic
Syntax:
S<g>-25VM[=<LV>,<DV>,<Dropout Time Delay>,<VM1>,<VM2>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-27 Command
Purpose:
Read/Set 27 pickup level, time delay, and mode.
Syntax:
S<g>-27<x>[=<Pickup>,<Time Delay>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-27R Command
Purpose:
Read/set (51)/27R control level and operating mode.
Syntax:
S<g>-27R[=<Pickup>,<Mode>]
Reference:
Section 4,
Protection and Control, Voltage Protection