13-36
Testing and Maintenance
BE1-951
Step 2 Using Table 13-44 as a guide, transmit the first row of setting commands to the relay.
Table 13-44. Trip and Alarm Pickup Settings
Over Excitation Settings
Purpose
TRIP
ALARM
S0-24=1.0,0.0,0.0
SA-24=50
Sets 24 PU at 1.0 V/H, Trip Time Dial=0, Reset Time Dial=0---Sets
24 Alarm at 50% of Trip PU
S0-24=2.0,0.0,0.0
SA-24=75
Sets 24 PU at 2.0 V/H, Trip Time Dial=0, Reset Time Dial=0---Sets
24 Alarm at 75% of Trip PU
S0-24=3.0,0.0,0.0
SA-24=95
Sets 24 PU at 3.0 V/H, Trip Time Dial=0, Reset Time Dial=0---Sets
24 Alarm at 95% of Trip PU
Step 3 Prepare to monitor the operation of the 24 Alarm and Trip functions. Alarm operation can be
verified by monitoring the Major Alarm LED on the relay's front panel. Operation of 24T by can be
verified by monitoring OUT1.
Step 4 Connect a 120 Vac, three-phase, 50 or 60-Hertz voltage source (depending on users nominal
frequency) to terminals C13 (A-phase), C14 (B-phase), C15 (C-phase) and C16 (Neutral). Refer
to Figure 13-1 for terminal locations.
Step 5 Apply A-phase voltage at nominal frequency and slowly increase until the Major Alarm LED lights
(V/H PU x Freq x % Alarm = PU). Pickup should occur 2 percent or 1 volt of the Alarm
setting. Continue increasing the A-phase voltage until OUT1 closes (V/H Trip x Freq = PU). Pickup
should occur 2 percent or 1 volt of the Trip pickup setting. Slowly decrease the A-phase
voltage until OUT1 opens. Dropout should occur between 97 and 98 percent of the actual pickup
value (Trip and Alarm). Verify the pickup and dropout accuracy of the middle and upper 24 Alarm
and Trip pickup settings listed in Table 13-41.
Step 6 Verify the 24 target on the HMI.
Step 7 (Optional) Repeat Steps 2 through 5 for frequencies other than nominal.
Step 8 (Optional) Repeat Steps 2 through 6 for the B-phase and C-phase voltage inputs.
Step 9 (Optional) Repeat Steps 2 through 7 for setting groups 1, 2, and 3.
Over Excitation, Volts/Hertz Trip Time Verification
Step 1 Using Table 13-45 as a guide, transmit the first row of setting commands to the relay.
Table 13-45. 24 Trip Time Settings
Settings
Purpose
S0-24=1.0,0.5,0.0
Sets 24 PU at 1.0 V/H, Trip Time Dial=0.5, Reset Time Dial=0
S0-24=1.0,2.0,0.0
Sets 24 PU at 1.0 V/H, Trip Time Dial=2.0, Reset Time Dial=0
S0-24=1.0,4.0,0.0
Sets 24 PU at 1.0 V/H, Trip Time Dial=4.0, Reset Time Dial=0
Table 13-46. 24 Trip Times
Multiple of
V/H Pickup
Time Dial 0.5
Time Dial 2.0
Time Dial 4.0
1.4
3.13 seconds
12.50 seconds
25.00 seconds
1.6
1.34 seconds
5.55 seconds
11.11 seconds
1.8
0.78 seconds
3.13 seconds
6.25 seconds