ASCII Command
Function
HMI Screen
BE1-951
Appendix
B-3
RG-TIME[=hr:mn:sc] or RG-TIME[=hr:mn<f>sc]]
Report/Set time.
4.6
RG-VER
Read program version, model number,
style number, and serial number.
4.7
RO-nA/B[#].CFG/DAT
Read oscillographic fault report.
N/A
RS[-n/Fn/ALM/IO/LGC/NEW][=0]
Read oscillographic
COMTRADE.DAT/.CFG fault report.
N/A
Table B-5. Setting Command
ASCII Command
Function
HMI Screen
S
Read all relay setting parameters.
N/A
Table B-6. Alarm Setting Commands
ASCII Command
Function
HMI Screen
SA
Read all major and minor alarm settings.
N/A
SA-BKR<n>[=<mode>,<alarm limit>]
Read/Set breaker alarm settings.
N/A
SA-DI<p>[=<alarm level>]
Read/Set demand alarm settings.
N/A
SA-DVAR[=<alm lvl>,<alm lvl>]
Read/Set var demand alarm setting.
N/A
SA-DWATT[=<alm lvl>,<alm lvl>]
Read/Set watt demand alarm setting.
N/A
SA-LGC[=<alarm num 1>[/<alarm num 2>] . . .
[<alarm num n>]]
Read/Set logic alarm setting mask.
N/A
SA-MIN[=<alarm num 1>[/<alarm num 2>] . . .
[<alarm num n>]]
Read/Set minor alarm setting mask.
N/A
SA-MAJ[=<alarm num 1>[/<alarm num 2>] . . .
[<alarm num n>]]
Read/Set major alarm setting mask.
N/A
SA-RESET[=<rst alm logic>]
Read/Set programmable alarms reset
logic.
N/A
Table B-7. General Setting Commands
ASCII Command
Function
HMI Screen
SG
Read all general settings.
N/A
SG-CLK[=<date format(M/D)>,<timeformat(12/24)>]
Read/Program time and date format .
N/A
SG-COM<#>[=<baud>,A<addr>,P<pglen>,
R<reply ack>,X<XON ena>]]
Read/Set serial communication protocol.
6.1.1-6.1.3
SG-CT<x>[=<CTratio>]
Read/Set Phase/Neutral CT ratio.
6.3.1, 6.3.2
SG-DI<x>[=<interval>]
Read/Set P(IA/IB/IC/var/watt), N and Q
demand interval.
N/A
SG-DSP[P/N]
Read analog signal dsp filter type.
N/A
SG-FREQ[=<freq(Hz)>]
Read/Enter power system frequency.
6.3.6
SG-HOLD<x>[=<1/0 hold ena>]
Read/Program output hold operation.
N/A
SG-ID[=<relayID>,<StationID>]
Read/Set relay ID and station ID used in
reports.
N/A
SG-IN<x>[=<Recognition Time>,<Debounce Time>]
Read/Set input recognition/denounce.
N/A