BE1-951 ASCII
Command
Interface
11-19
S<g>-32 Command
Purpose:
Read/Set Logic for 32 Function Modules
Syntax :
S<g>-32[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control
S<g>-47 Command
Purpose:
Read/Set 47 pickup level and time delay.
Syntax:
S<g>-47[=<Pickup>,<Time Delay>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-50T Command
Purpose:
Read/Set 50TN pickup level and time delay.
Syntax:
S<g>-<x>50T<p>[=<Pickup>,<Time Delay>,<Direction>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
S<g>-51 Command
Purpose:
Read/Set 51 pickup level, time delay, and curve.
Syntax:
S<g>-51<p>[=<Pickup>,<Time Delay>,<Curve>,<direction>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
S<g>-59 Command
Purpose:
Read/Set 59 pickup level, time delay, and mode.
Syntax:
S<g>-<x>59<p>[=<Pickup>,<Time Delay>]
Reference:
Section 4,
Protection and Control, Voltage Protection
S<g>-62 Command
Purpose:
Read/Set 62 time delay.
Syntax:
S<g>-<x>62[=<T1>,<T2>]
Reference:
Section 4,
Protection and Control, General Purpose Logic Timers (62/162)
S<g>-67N Command
Purpose:
Read/Set 67 Neutral Polarizing Mode and Quantities
Syntax : S<g>-67N[=<mode>,<quantity>}]
Reference:
Section 4,
Protection and Control
S<g>-79 Command
Purpose:
Read/Set 79 time delay.
Syntax:
S<g>-79<x>[=<Time Delay>]
Reference:
Section 4,
Protection and Control, Reclosing
S<g>-79SCB Command
Purpose:
Read/Set 79 Sequence Controlled Block Output.
Syntax:
S<g>-79SCB[=<step list>]
Reference:
Section 4,
Protection and Control, Reclosing
S<g>-81 Command
Purpose:
Read/Set 81 pickup level, time delay, and mode.
Syntax:
S<g>-<x>81[=<Pickup>,<Time Delay>,<Mode>]
Reference:
Section 4,
Protection and Control, Frequency Protection
S<g>-81INH Command
Purpose:
Read/Set 81 undervoltage inhibit level.
Syntax:
S<g>-81INH[=<Pickup>]
Reference:
Section 4,
Protection and Control, Frequency Protection