13-68
Testing and Maintenance
BE1-951
Table 13-107. Binary Group Control Select and Operate Commands
Command
Purpose
A=
Gain write access
CS-43=0
Selects 43 for FALSE operation
CO-43=0
Executes 143 FALSE operation
EXIT
Exit select and operate mode
Step 4 Verify that VO1 goes FALSE and opens OUT1 when SG0 becomes the active setting group.