BE1-951
Testing and Maintenance
13-67
Command
Purpose
CO-43=1
Executes 43 TRUE operation
CS-43=0
Selects 43 for FALSE operation
CO-43=0
Executes 43 FALSE operation
CS-243=1
Selects 243 for TRUE operation
CO-243=1
Executes 243 TRUE operation
CS-243=0
Selects 243 for FALSE operation
CO-243=0
Executes 243 FALSE operation
CS-343=1
Selects 343 for TRUE operation
CO-343=1
Executes 343 TRUE operation
EXIT
Exit select and operate mode
Step 3 Use the RS-LGC command to retrieve logic variable data from the SER. Verify that the setting
group change actions were logged.
Manual Change - Mode 2
Manual Change Mode 2 test procedures are a continuation of the Mode 1 test procedures. Do not change
the logic or settings except for those in Step 1 and subsequent.
Step 1
Transmit the commands in Table 13-106 to the relay. These commands set up the relay for binary
setting group control selection.
Table 13-106. Binary Group Control Selection Setup
Command
Purpose
A=
Gain write access
SL-GROUP=2,43,0,0,0,143
Configures the setting group control function as binary
coded selection.
D0 logic=43 D1, D2, or D3 logic=0
Auto Logic=143
SL-43=2
Sets 43 to On/Off mode
EXIT;Y
Exit and save settings.
Step 2 Verify that VO1 went TRUE and closed OUT1 when SG1 became the active setting group (with
443=1, setting group 1 is selected). For more information on setting group selection, see Section
4,
Protection and Control , Setting Groups.
Step 3 Transmit the select and operate commands in Table 13-107 to the relay.