BE1-951
Installation
12-19
Notes:
°
1.
The neutral ground (I
N
) operates on internally calculated residual (3Io) current
2.
VTP connections shown are for H1 case. See Figure 12-13 for S1 case connections
3.
4-wire connection shown as typical. See Figure 12-20 for alternate VTP connections
4.
CT polarity connected to relay polarity, power flow from High Side to Low Side defined as
power out and = "+" watts
5. Optional Independent Ground Input (IG) connected to detect low side ground faults
Figure 12-22. OC Protection of a Delta-Wye Grounded Transformer (Radial Load) with Optional
Independent Ground Input (IG) Connected for Low Side Ground Fault Protection