11-20
ASCII Command Interface
BE1-951
SP-60FL Command
Purpose:
Read/Set loss of potential pickup setting.
Syntax:
SP-60FL[=<I_Blk>,<V_Blk>]
Reference:
Section 4,
Protection and Control, VT Fuse Loss Detection (60FL)
SP-BF Command
Purpose:
Read/Set the breaker failure timer setting.
Syntax:
SP-BF[=<Time Delay>]
Reference:
Section 4,
Protection and Control, Breaker Failure Protection
SP-CURVE Command
Purpose:
Read/Set the user programmable 51 curve parameters.
Syntax:
SP-CURVE[=<A>,<B>,<C>,<N>,<R>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
SP-GROUP Command
Purpose:
Read/Program auxiliary setting group auto operation.
Syntax:
SP-GROUP<x>=[<sw_time>,<sw_level>,<ret_time>,<ret_level>,<prot_elem>]
Reference:
Section 4,
Protection and Control, Setting Groups
SP-79ZONE Command
Purpose:
Read/Set 79 zone sequence logic.
Syntax:
SP-79ZONE[=<zone pickup logic>]
Reference:
Section 4,
Protection and Control, Reclosing
Global Commands
GS-PW Command
Purpose:
Read or change a password.
Syntax:
GS-PW<x>[=<password>,<com ports(0/1/2)>]
Reference:
Section 9,
User Interface and Security Setup, User Interface