13-54
Testing and Maintenance
BE1-951
Command
Purpose
Y
Confirm overwrite
SL-N=MODE3
Sets MODE3 as custom logic name
SL-243=3
Sets 243 switch for Mode 3 operation
SL-VO1=243
Enables OUT1 to close for 243
EXIT;Y
Exit and save settings.
Step 2 Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester may be used to
monitor the contact status of OUT1.
Step 3
Transmit the commands in Table 13-83 to the relay. These commands pulse the 243 switch on and
off once.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state.
Table 13-83. x43 Mode 3 Pulse Commands
Command
Purpose
A=
Gain write access
CS-243=P
Selects 243 for On operation
CO-243=1
Executes 243 for On operation
Virtual Breaker Control Switch
Purpose: To verify 101 virtual breaker control switch operation.
Reference Commands: SL-101, CS/CO-101C, CS/CO-101T
Step 1 Prepare the 101 virtual breaker control switch for testing by transmitting the commands in Table
13-84 to the relay.
Table 13-84. 101 Virtual Breaker Control Switch Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with logic=none settings.
Y
Confirm overwrite
SL-N=S101
Sets S101 as custom logic name
SL-101=1
Enables 101 switch
SL-VO1=101T
Enables OUT1 to close when 101T is TRUE
SL-VO1=101C
Enables OUT2 to close when 101C is TRUE
SL-VO1=101SC
Enables OUT3 to close when 101SC is TRUE
EXIT;Y
Exit and save settings.