13-30
Testing and Maintenance
BE1-951
Table 13-34. 50TP, 50TN, and 50TQ Directional Pickup Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with
logic=none settings.
Y
Confirm overwrite
SG-VTP=1,4W,PN,PN
Set VT phase voltage parameters
SG-VTX-1,AN
Set auxiliary voltage parameters
SL-N=67
Sets custom logic name
SL-50TP=1,0
Enables 50TP and disables blocking
SL-50TN=1,0
Enables 50TN and disables blocking
SL-50TQ=1,0
Enables 50TQN and disables blocking
SL-VO1=50TPT
Enables OUT1 to close for 50TPT trip
SL-VO2=50TNT
Enables OUT2 to close for 50TNT trip
SL-VO3=50TQT
Enables OUT3 to close for 50TQT trip
SG-TRIG=50TPT+50TNT+50TQT,
50TQPU,0
Enable 50TP, 50NT, 50QT to log and trigger fault
recording
SG-CT=1
Sets P, N CT ratio at 1:1
SG-LINE=8,80,24,80,100
Set Line conditions
EXIT;Y
Exit and save settings
Step 2 Using Table 13-35 as a guide, transmit the 67 setting commands to the relay. Prior to each
directional test, reset the relay targets (HMI Screen) from the previous test.
Table 13-35. 67P-50TP Operational Settings
Operating Settings
Purpose
S0-67=Q
Sets 67N to Negative Sequence Polarizing
S0-50TP=2.5,0,F
Sets 50TP at 2.5 amps, 0 time delay, Forward Tripping Direction
S0-50TN=0,0,F
Sets 50TN at 0 amps, 0 time delay, Forward Tripping Direction
S0-50TQ=0,0,F
Sets 50TN at 0 amps, 0 time delay, Forward Tripping Direction
Positive Sequence Voltage Polarizing, Phase Overcurrent Elements
Step 3 Connect and apply a 120 Vac, three-phase voltage source at nominal frequency to terminals C13
(A-phase), C14 (B-phase), C15 (C-phase) and C16 (Neutral). Connect a variable ac current source
to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity). Refer to Figure 13-1 for terminal
locations.
Step 4 Apply 0 amps A-phase current at an angle of 80 degrees I lag E (positive sequence line angle) and
slowly increase the current until OUT1 closes. Decrease A-phase current until OUT1 just drops out.
Pickup will occur 2 percent of the 50TP pickup setting. Dropout will occur at 93 to 97% of
actual pickup. Verify 67A target on the HMI.