BE1-951
Metering
5-3
Metering Function
Serial Command
HMI Screen
Current, Neutral
M-IN
3.7
Frequency
M-FREQ
3.10
Power Factor
M-PF
3.9
Power, Apparent (VA)
M-S
3.9
Power, Reactive
M-VAR
3.8
Power, True
M-WATT
3.8
Voltage, all values
M-V
N/A
Voltage, A-phase
M-VA
3.1
Voltage, B-phase
M-VB
3.1
Voltage, C-phase
M-VC
3.1
Voltage, A-phase to C-phase
M-CA
3.2
Voltage, B-phase to C-phase
M-VBC
3.2
Voltage, A-phase to B-phase
M-VAB
3.2
Voltage, Negative Sequence
M-V2
3.4
Voltage, Zero Sequence
M-3V0
3.4
Voltage Auxiliary
M-VX
3.3
Voltage Three-phase Auxiliary
M-V3X
3.3
Metered sync angle between Phase and Aux inputs
M-SYNC
3.11
METERING COMMAND DESCRIPTIONS
The following paragraphs describe each metering command and provide examples for using the commands.
M Command
Purpose:
Reads all metered values.
Syntax:
M
Comments: This command returns all measured and calculated metered data.
M Command Example
Read all metered values.
>M
M-VA=119V; M-VB=119V; M-VC=118V; M-VAB=206V
M-VBC=205V; M-VCA=206V; M-V2=0.30V; M-VX=0.40V
M-V3X=1.25V
M-3V0=0.30V
M-IA=4.99A; M-IB=5.00A; M-IC=4.99A; M-IN=0.00A
M-IQ=0.02A; M-IG=4.99A
M-WATT3= 3.44KW; M-WATTA= 2.30KW; M-WATTB= 2.30KW; M-WATTC= 2.29KW
M-VAR3= 2.45KVAR; M-VARA= 1.30KVAR; M-VARB= 1.30KVAR; M-VARC= 1.30KVAR
M-S=1.78KVA
M-PF=+1.00 LEAD
M-FREQP=60Hz; M-FREQX=60Hz; M-FREQS= 600Hz
M-SYNC=