BE1-951
Testing and Maintenance
13-55
Step 2 Prepare to monitor the 101 virtual breaker control switch operation. Operation can be verified by
monitoring the programmed output contacts, HMI screen 2.2.1, or by using RG-STAT command.
See Section 6,
Reporting and Alarm Functions for more information.
Step 3
Transmit the commands in Table 13-85 to the relay. These commands place the 101 switch in the
trip position.
Result: OUT1 closes for 200 milliseconds and returns to the open state. OUT3 opens (trip state) and
remains open.
Table 13-85. 101 Virtual Breaker Control Switch Trip Test Commands
Command
Purpose
A=
Gain write access
CS-101T=T
Selects 101T for Trip operation
CO-101T=T
Executes 101T for Trip operation
Step 4
Transmit the commands in Table 13-86 to the relay. These commands place the 101 switch in the
closed state.
Result: OUT2 closes for 200 milliseconds and returns to the open state. OUT3 closes (close state) and
remains closed.
Table 13-86. 101 Virtual Breaker Control Switch Close Test Commands
Command
Purpose
CS-101C=C
Selects 101C for Close operation
CO-101C=C
Executes 101C for Close operation
Virtual Lockout (Latch)
Purpose: To verify 86, 186 virtual lockout operation.
Reference Commands: SL-86, SL-186
Step 1
Prepare the 87 virtual lockout for testing by transmitting the commands in Table 13-90 to the relay.
Table 13-87. 86, 186 Virtual lockout Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings.
Overwrite with logic=none settings.
Y
Confirm overwrite
SL-N=LO_86
Sets LO_86 as custom logic name
SL-86=1, IN1, IN2
Enables 86 lockout latch, IN1=Trip,
IN2=Reset
SL-VO1=86
Enables OUT1 to close when 86 is
TRUE
EXIT;Y
Exit and save settings.
Step 2 Prepare to monitor the 86 virtual lockout operation. Operation can be verified by monitoring OUT
1 at HMI screen 1.5.2, or monitoring OUT1 contacts between terminals C1 and C2, or by using the
RG-STAT command. See Section 6,
Reporting and Alarm Functions for more information.
Step 3 Connect negative or non-polarity power supply voltage (PSV) to Input 1 and 2 terminals B2 and
B4.