13-46
Testing and Maintenance
BE1-951
Command
Purpose
SL-281=1,0
Enables 281, disables blocking
SL-381=1,0
Enables 381, disables blocking
SL-481=1,0
Enables 481, disables blocking
SL-581=1,0
Enables 581, disables blocking
SL-VO1=81T+581T
Enables OUT1 to close for 81 or 581 trip
SL-VO2=181T
Enables OUT2 to close for 181 trip
SL-VO3=281T
Enables OUT3 to close for 281 trip
SL-VO4=381T
Enables OUT4 to close for 381 trip
SL-VO5=481T
Enables OUT5 to close for 481 trip
EXITY;Y
Exit and save settings
Step 2 Transmit the commands in Table 13-65 to the relay. These commands set the pickup value and
operating mode (Underfrequency or Overfrequency) for each of the x81 functions.
Table 13-65. x81 Pickup and Mode Settings
Pickup and
Mode Settings
Purpose
S0-81=42,0,U
Sets 81 PU at 42 Hz, underfrequency
S0-181=46,0,U
Sets 181 PU at 46 Hz, underfrequency
S0-281=48,0,U
Sets 281 PU at 48 Hz, underfrequency
S0-381=65,0,O
Sets 381 PU at 65 Hz, overfrequency
S0-481=67,0,O
Sets 481 PU at 67 Hz, overfrequency
S0-581=69,0,O
Sets 581 PU at 69 Hz, overfrequency
Step 3 Prepare to monitor x81 function operation. Operation can be verified by monitoring the
programmed output contacts or HMI Screen 1.5.2.
Step 4 Connect and apply a 120 Vac, 60 hertz voltage source to terminals C13 (A-phase) and C16
(Neutral).
Step 5
Slowly decrease the frequency of the applied voltage until OUT3 (281)closes. Pickup should occur
0.01 hertz of the pickup setting. Slowly increase the frequency until OUT3 opens. Dropout
should occur at 0.02 hertz above or below the pickup setting.
Step 6 Repeat Step 5 for the 181 (OUT2) and 81 (OUT1) functions.
Step 7 Repeat Step 4.
Step 8
Slowly increase the frequency of the applied voltage until OUT4 (381) closes. Pickup should occur
0.01 hertz of the pickup setting. Slowly decrease the frequency until OUT4 opens. Dropout
should occur at 0.02 hertz above or below the pickup setting.
Step 9 Repeat Step 5 for the 481 (OUT5) and 581 (OUT1) functions.
Step 10 Connect and apply, 120 Vac, 60Hz voltage source to Vx input C17 and C18.
Step 11 Repeat steps 5 through 9.
Step 12 (optional)Repeat Steps 1 through 11 for setting groups 1,2, and 3.