BE1-951
Testing and Maintenance
13-23
Step 2 Prepare the 50TN and 150TN elements for testing by transmitting the commands in Table 13-19 to
the relay. Reset targets.
Table 13-19. 50/150TN Pickup Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom settings.
Overwrite with logic=none settings.
Y
Confirm overwrite
SL-N=50/150TN
Sets 50/150TN as custom logic name
SL-50TN=G,0
Enables 50TN for IG input, disables blocking
SL-150N=G,0
Enables 150TN for IG input, disables blocking
SL-VO1=50TNT
Enables OUT1 to close for 50TN trip
SL-VO2=150TNT
Enables OUT2 to close for 150TN trip
SG-CT=1
Sets CT ratio at 1
SG-TRIGGER=50TNT+150TNT,
150TNPU,0
Enable 50/150TNT to log and trigger fault
recording
EXITY;Y
Exit and save settings
Step 3 Using Table 13-20, transmit the first row of setting commands for your sensing input type.
Table 13-20. 50/150TN Pickup Commands
Sensing Type
Command
Comments
1 A
S0-50TN=0.1,0,N S0-150TN=0.1,0,N
Sets 50TN pickup at 0.1 A,TD=0,
non-directional Sets 150TN pickup at
0.1 A,TD=0, non-directional
S0-50TN=1.0,0,N S0-150TN=1.0,0,N
Sets 50TN pickup at 1.0 A,TD=0,
non-directional Sets 150TN pickup at
1.0 A,TD=0, non-directional
S0-50TN=5.0,0,N S0-150TN=5.0,0,N
Sets 50TN pickup at 5.0 A,TD=0,
non-directional Sets 150TN pickup at
5.0 A,TD=0, non-directional
5 A
S0-50TN=0.5,0,N S0-150TN=0.5,0,N
Sets 50TN pickup at 0.5 A,TD=0,
non-directional Sets 150TN pickup at
0.5 A,TD=0, non-directional
S0-50TN=5.0,0,N S0-150TN=5.0,0,N
Sets 50TN pickup at 5.0 A,TD=0,
non-directional Sets 150TN pickup at
5.0 A,TD=0, non-directional
S0-50TN=10.0,0,N S0-150TN=10.0,0,N
Sets 50TN pickup at 10.0 A,TD=0,
non-directional Sets 150TN pickup at
10.0 A,TD=0, non-directional
Step 4 Slowly increase the IG current until OUT1 closes. Verify that pickup occurs within the specified
accuracy listed in Table 13-21. Slowly decrease the applied current until OUT1 opens. Dropout
should occur at 93 to 97 percent of pickup.