Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
BE1-951
Application
8-29
VO10
Breaker Failure
Initiate
Initiate breaker failure timing when
protective trip expression is TRUE.
BFI
INI
NORMAL
BESTlogic Expression: VO10 = VO11
VO11
Protective Trip
Expression
TRUE when any 50, 150, or 51
element has timed out.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression
TRUE when any 50, 150, or 51
element has picked up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12 =
51PPU+51NPU+51QPU
VO13
Alarm Mask 21
Not used.
VO13
TRUE
FALSE
BESTlogic Expression: VO13 = 0
VO14
Alarm Mask 22
Not used.
VO14
TRUE
FALSE
BESTlogic Expression: VO14 = 0
VO15
Alarm Mask 23
Indicates that the relay is in Test
mode and that the breaker failure is
disabled. TRUE if IN4 is de-
energized or if virtual switch 343 is
closed.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15 = /IN4+343