8-4
Application
BE1-951
Function
Purpose
BESTlogic
Expression
Mode Setting
51Q
Used for timed negative sequence overcurrent
protection.
0
1 (enabled)
151N
None
0
0 (disabled)
27P
None
0
0 (disabled)
59P
None
0
0 (disabled)
59X
None
0
0 (disabled)
47
None
0
0 (disabled)
62
None
0
0 (disabled)
162
None
0
0 (disabled)
79
None
0
0 (disabled)
81
None
0
0 (disabled)
181
None
0
0 (disabled)
281
None
0
0 (disabled)
381
None
0
0 (disabled)
481
None
0
0 (disabled)
581
None
0
0 (disabled)
BF
None
0
0 (disabled)
GROUP
Input 0 Logic: No manual selection logic is used.
0
1
(discrete input
selection)
Input 1 Logic: No manual selection logic is used.
0
Input 2 Logic: No manual selection logic is used.
0
Input 3 Logic: No manual selection logic is used.
0
Auto/Manual Logic: Set to 1 (/0) to enable automatic
selection. No manual selection is used.
/0
Table 8-3. BASIC-OC Virtual Switch Logic
Switch
Purpose
Mode
Variable Label
State Labels
TRUE (1)
FALSE (0)
43
Not used
0 (disabled)
SWITCH_43
CLOSED
OPEN
143
Not used
0 (disabled)
SWITCH_143
CLOSED
OPEN
243
Not used
0 (disabled)
SWITCH_243
CLOSED
OPEN
343
Not used
0 (disabled)
SWITCH_343
CLOSED
OPEN
101
Not used
0 (disabled)
N/A
N/A
N/A
Table 8-4. BASIC-OC Virtual Output Logic
Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
VOA
(OUTA)
Alarm Output Contact.
Alarm contact closes automatically
when relay trouble alarm occurs.
ALARM
ACTIVE
NORMAL
BESTlogic Expression: VOA = 0
VO1
(OUT1)
Breaker Trip Contact.
Contact closes when protective trip
expression is TRUE.
BKR_TRIP
TRIP
NORMAL