BE1-951
Metering
5-5
2.
Read the voltage across phases C and A.
>M-VCA
206V
M-VAR Command
Purpose:
Read metered 3 Phase Vars in primary units.
Syntax:
M-VAR[<phase>]
Comments: phase = 3/A/B/C
M-VAR Command Example
Read the system reactive power.
>M-VARA
-0.05KVAR
M-3V0 Command
Purpose:
Read metered voltage (V) in primary units
Syntax:
M-3VO
Comments: Reports “NA” unless VTP connection is 4-wire.
M-3V0 Command Example.
Read the zero-sequence voltage.
>M-3V0
0.30V
M-WATT Command
Purpose:
Read metered 3 Phase Watts (W) in primary units.
Syntax:
M-WATT[<phase>]
Comments: phase = 3/A/B/C
M-WATT Command Example
Read the system watts.
>M-WATTA
1.78KW
M-SYNC Command
Purpose:
Read metered sync angle between Phase and Aux inputs
Syntax : M-SYNC
M-SYNC Command Example
>M-SYNC
20.0 Deg