BE1-951 ASCII
Command
Interface
11-9
SG-COM0 Command Example
1.
Program front port for 1200 baud
>SG-COM0 = 1200
2.
Read the protocol setting for rear RS-485 port.
>SG-COM2
19K, A156,P0,R1,X0
3.
Read settings for all ports.
>SG-COM
SG-COM0=1200,P24,R1,X1
SG-COM1=9600,A0,P24,R1,X1
SG-COM2=19K,A156,P0,R1,X0
COMMAND SUMMARY
Miscellaneous Commands
ACCESS Command
Purpose:
Read/Set access level in order to change settings.
Syntax:
ACCESS[=<password>]
Reference:
Section 11,
ASCII Command Interface, Miscellaneous Command Descriptions
EXIT Command
Purpose:
Exit programming mode.
Syntax:
EXIT Note: Relay will prompt for verification.
Reference:
Section 11,
ASCII Command Interface, Miscellaneous Command Descriptions
HELP Command
Purpose:
Obtain help with command operation.
Syntax:
HELP <cmd> or H <cmd> gives help with a command; H1 gives command list
Reference:
Section 11,
ASCII Command Interface, Miscellaneous Command Descriptions
Metering Commands
M Command
Purpose:
Read all metered values.
Syntax:
M
Reference:
Section 5,
Metering, Metering Command Descriptions
M-FREQ Command
Purpose:
Read metered frequency.
Syntax:
M-FREQ
Reference:
Section 5,
Metering, Metering Command Descriptions
M-I Command
Purpose:
Read metered current in primary unit.
Syntax:
M-I[<phase>]
Reference:
Section 5,
Metering, Metering Command Descriptions
M-PF Command
Purpose:
Read metered three-phase power factor.
Syntax:
M-PF
Reference:
Section 5,
Metering, Metering Command Descriptions