5-4
Metering
BE1-951
M-FREQ Command
Purpose:
Read metered frequency (F)
Syntax :
M-FREQ[<source>]
Comments: Frequency is measured from A-phase to Neutral on four-wire sensing systems and A-phase
to B-phase on three-wire sensing systems.
Phase = P/X/S for phase/Auxiliary/Slip
M-FREQ Command Example
Read the power system frequency.
>M-FREQ
M-FREQP=58.00Hz; M-FREQX=60.00Hz; M-FREQS=2.00Hz
M-I Command
Purpose:
Read metered current in primary units.
Syntax:
M-I[<phase>]
Comments: phase = A/B/C/N/Q/G or no entry
M-I Command Examples
1.
Read metered current values.
>M-I
M-IA=4.99A;
M-IB=5.00A;
M-IC=4.99A;
M-IN=0.00A
M-IQ=0.02A;
M-IG=4.99A
2.
Read the Phase-C current
>M-IC
4.99A
M-PF Command
Purpose:
Read the three-phase power factor.
Syntax:
M-PF
M-PF Command Example
Read the system power factor.
>M-PF
+1.00 LEAD
M-S Command
Purpose:
Read the three-phase apparent power (VA).
Syntax:
M-S
M-S Command Example
Read the system apparent power.
>M-S
1.78KVA
M-V Command
Purpose:
Read metered voltage values.
Syntax:
M-V[<phase>]
Comments: phase = A/B/C/AB/BC/CA/2/X/3X or no entry
M-V Command Examples
1.
Read all voltage values.
>M-V
M-VA=119V;
M-VB=119V;
V-VC=118V;
M-VAB=206V
M-VBC=205V;
M-VCA=206V;
M-V2=0.30V;
M-VX=0.30V
M-V3X=0.30V