Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
BE1-951
Application
8-39
VO13
Feeder Backup Mode
Alarm.
TRUE when in Setting Group 1.
FEEDER_BU
BACKUP
NORMAL
BESTlogic Expression: VO13 = SG1
VO14
Not Used
VO14
TRUE
FALSE
BESTlogic Expression: VO14 = 0
VO15
Test Mode.
Blocks the BFI signal (VO3) to an
external breaker failure relay.
TRUE when IN4 de-energizes or
virtual switch 343 closes.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15 = /IN4+343