BE1-951 ASCII
Command
Interface
11-17
SL-43 Command
Purpose:
Read/Set Logic for Virtual switches.
Syntax:
SL-<x>43[=mode]
Reference:
Section 4,
Protection and Control, Virtual Switches
SL-47 Command
Purpose:
Read/Set logic for 47 function modules.
Syntax:
SL-47[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Voltage Protection
SL-50T Command
Purpose:
Read/Set logic for x50 function modules.
Syntax:
SL-<x>50T<p>[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
SL-51 Command
Purpose:
Read/Set logic for 51 function modules.
Syntax:
SL-<x>51<p>[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
SL-101 Command
Purpose:
Read/Set Logic for Virtual Breaker switch (101)
Syntax:
SL-101[=<mode>]
Reference:
Section 4,
Protection and Control, Overcurrent Protection
SL-59 Command
Purpose:
Read/Set logic for 59 function modules.
Syntax:
SL-<x>59P[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Voltage Protection
SL-62 Command
Purpose:
Read/Set logic for 62 function modules.
Syntax:
SL-<x>62[=<mode>,<INI logic>,<BLK logic>]
Reference:
Section 4,
Protection and Control, General Purpose Logic Timers (62/162)
SL-79 Command
Purpose:
Read/Set logic for 79 function
Syntax:
SL-79[=<mode,<RI logic>,<STATUS logic>,<WAIT logic>,<LOCKOUT logic>]
Reference:
Section 4,
Protection and Control, Reclosing
SL-81 Command
Purpose:
Read/Set logic for 81 function modules.
Syntax:
SL-<x>81[=<mode>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Frequency Protection
SL-86 Command
Purpose:
Read/Set Logic for 86 Function Modules
Syntax:
SL-<x>86[=<mode>,<Trip logic>,<Reset Logic>]
Reference: Section
4,
Protection and Control
SL-BF Command
Purpose:
Read/Set logic for breaker failure function modules.
Syntax:
SL-BF<x>[=<mode>,<INI logic>,<BLK logic>]
Reference:
Section 4,
Protection and Control, Breaker Failure Protection