8-32
Application
BE1-951
SL-59P:0,0; SL-59X:0,0
SL-47:0,0
SL-62:0,0,0
SL-162:0,0,0
SL-79:1,VO8,/IN1,VO12,VO9+VO15
SL-81:0,0
SL-181:0,0
SL-281:0,0
SL-381:0,0
SL-481:0,0
SL-581:0,0
SL-BF:1,VO10,VO15
SL-GROUP:1,0,0,0,0,/43
SL-43:2
SL-143:2
SL-243:2
SL-343:2
SL-101:1
SL-VOA:0
SL-VO1:BFPU+VO11+101T
SL-VO2:79C+101C
SL-VO3:/VO15
SL-VO4:/VO5*VO12*/VO15
SL-VO5:BFT
SL-VO6:0
SL-VO7:0
SL-VO8:VO11
SL-VO9:143+VO5+/IN2
SL-VO10:VO11
SL-VO11:50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO12:51PPU+51NPU+51QPU
SL-VO13:0
SL-VO14:0
SL-VO15:343+/IN4
BUS AND BACKUP LOGIC SCHEMES
Logic schemes BUS and BACKUP are intended for use on a bus main breaker and provide all overcurrent
protection and control functions required for a typical bus main breaker in a nondirectional overcurrent
protection application. When used with other programmable relays using the FDR-W-IL scheme, BUS and
BACKUP logic provide complete overcurrent protection for the transformers, bus, and feeders in a radial
system substation.
Interconnection of a relay using FDR-W-IL logic with relays using BUS and BACKUP logic provides complete
backup protection (except for reclosing) for the feeder relays if they are out of service for testing or
maintenance. Figure 8-9 illustrates how FDR-W-IL, BUS, and BACKUP relays are interconnected to achieve
this integrated protection system.
The components of BUS logic are summarized in Tables 8-17, 8-18, 8-19, and 8-20. A diagram of BUS logic
is shown in Figure 8-10. Figure 8-11 shows a one-line drawing for the BUS logic scheme.
The components of BACKUP logic are summarized in Tables 8-21, 8-22, 8-23, and 8-24. A diagram of
BACKUP logic is shown in Figure 8-12. Figure 8-13 shows a one-line drawing for the BACKUP logic
scheme.