CHAPTER 3: USING PROGRAMMING FUNCTIONS
IS-2200CA/4500CA INVERTER POWER SUPPLY
990-412
3-41
WELD STOP OFF T IME
Set va lue
We ld ing stop
s igna l input
e. MONITOR FIRST TIME
Use this setting to specify the start time to measure the monitored value (current, voltage, power,
pulse width). The start time can be set in a range from 0 to 15ms.Use this setting to exclude the
initial rise of current from measurement.
The monitored value will not be displayed if the weld time is shorter than
MONITOR FIRST
TIME
. The monitored value will not be also checked against the upper and lower tolerance limits.
t
Monitor measurement
Weld Time WELD1, WELD2, WELD3
t = MONITOR FIRST TIME
~
~
f. MONITOR SLOPE MODE
Select whether or not to include a slope period in the monitored value to be displayed.
EXCLUDE
Slope period will not be included.
INCLUDE
Slope period will be included.
g. WELD STOP OFF TIME
Sets the neglecting time of the welding stop signal for each of
WELD1
,
WELD2
and
WELD3
.
Even if the welding stop signal is input during welding, the current is supplied for the set time
and the sequence will switch to the next.
When the welding stop signal is input within WELD STOP OFF TIME
The welding is stopped at the end of WELD STOP OFF TIME.