CHAPTER 3: USING PROGRAMMING FUNCTIONS
IS-2200CA/4500CA INVERTER POWER SUPPLY
990-412
3-13
control, and secondary constant-voltage effective value control. Though 1 is normally used, the
larger value will give the shorter rise time. (Invalid in the primary constant-current peak value
control and the constant-phase control.)
NOTE:
Control gain refers to a correction amount in feedback control. Although the current
rises more rapidly with greater control gain, the current waveform may experience overshoot.
On the other hand, a smaller control gain suppresses current waveform overshoot but causes a
slower increase in current. The Power Supply offers nine 9 choices of gain levels.
k. TURN RATIO
Set the welding transformer turns ratio. The turns ratio can be set in a range from 001.0 to 199.9.
NOTE:
When using the primary constant-current effective value control or primary constant-
current peak value control, always set the correct turns ratio.
An incorrect ratio will result in incorrect output.
NOTE:
When using the primary constant-current effective value control or primary constant-
current peak value control, always set the correct turns ratio.
An incorrect ratio will result in incorrect output.
l. TRANS #
Keep set to 1. Feature is not active.
m.
REV
When the cursor ( ) is displayed, pressing the
ENTER
key will change the display to Current
and time setting screen.
Large contro l ga in
Sett ing
Sma l l contro l ga in
Sett ing
Overshoot
S low increase in current