APPENDIX B. ELECTRICAL AND DATA CONNECTIONS
IS-2200CA/4500CA INVERTER POWER SUPPLY
990-412
B-21
PIN
NAME
DESCRIPTION
36
37
VALVE1 (SOL1)
VALVE2 (SOL2)
Solenoid valve output pins. 36: VALVE1 (SOL1); 37: VALVE2 (SOL2)
These pins are closed for the duration of the STAGE 2 input.
Output between SQD and HOLD.
When the off time (OFF) is set, this pin is output between SQZ and HOLD after the
second sequence.
The contacts are rated at 120V AC or 24V AC/DC at 0.5A (semiconductor
switches).
Use a solenoid valve with a current capacity of 0.5A or less.
38
39
SECONDARY
VOLTAGE
Secondary voltage input pins. Internally connected to the IT XFMR sense connector.
If IT XFMR sense cable not used may be connected directly to electrodes.
40
INT +24VDC OUT
Jumpered from Pin1 to provide drive voltage to Contactor Solid State Relay
41
CONTACTORS
Switch closure between Pin 40 and Pin 41 will engage the optional contactor
42
CONTACTOR N.O.
Detect position of contactors between pin 42 and 43: contactors normally open
(optional)
43
CONTACTOR COM
Contactor Aux contact common (optional)
44
CONTACTOR N.C.
Detect position of contactors between pin 44 and 43: contactors normally closed
(optional)
45
46
CURRENT COIL
Current coil input, used for secondary current feedback. Internally connected to the
IT XFMR sense connector. If XFMR sense cable not used may be connected
external current coil.
47
N/A
UNUSED
48
VALVE COM
COMMON for all valves
49
50
51
52
53
54
55
EX VALVE1 (EX
SOL1)
EX VALVE2 (EX
SOL2)
EX VALVE3 (EX
SOL3)
EX VALVE4 (EX
SOL4)
RET VALVE1 (RET
SOL1)
RET VALVE2 (RET
SOL2)
VALVE RELAY
(SOL RELAY)
Solenoid valve output pins. 49: EX VALVE1 (EX SOL1); 50: EX VALVE2 (EX
SOL2); 51: EX VALVE (EX SOL3); 52: EX VALVE4 (EX SOL4)
Retraction Solenoid valve output pins. 53: RET VALVE1 (RET SOL1); 54: RET
VALVE2 (RET SOL2); 55: VALVE RELAY (SOL RELAY)
The contacts are rated at 120V AC or 24V AC/DC at 0.5A (semiconductor
switches).
Use a solenoid valve with a current capacity of 0.5A or less.
56
INT +24VDC GND
(I/O COM)
COM pin. This pin is internally connected to the +24VDC GND
Summary of Contents for S-2200CA