APPENDIX B. ELECTRICAL AND DATA CONNECTIONS
IS-2200CA/4500CA INVERTER POWER SUPPLY
990-412
B-9
PIN
NAME
DESCRIPTION
TB1-14
WELD
COUNT/WE2
STOP
WE2 stop input or Weld count input pin.
When WE2 STOP is selected
Closing this pin during the WELD2 sequence will switch the sequence to COOL2.
Closing this pin in the sequence other than WELD2 is neglected. The sequence will
switch to COOL2 if this signal is closed during the WELD2 sequence operation.
When this pin is closed before WELD2 welding start after startup, the current is
supplied for at least a control cycle and WELD2 is stopped to switch the sequence to
COOL2.
When WELD COUNT is selected
This pin allows you to determine whether or not the number of deposited welds has
reached the WELD COUNT setting.
20ms or more is required for receiving the WELD COUNT input signal.
TB1-15
EXT. COM
For internal Sink (pull down) Connect to pin 1. For Internal Source (push up)
Connect to pin 4.
To activate input in Sink Mode, connect inputs to INT +24VDC GND (I/O COM)
To activate input in Source Mode, connect inputs to INT +24VDC
For External Sink attach PLC +24V. For External Source, attach PLC COM
TB1-16
INT +24VDC GND
(I/O COM)
COM pin. This pin is internally connected to the +24VDC GND
TB2-1
STAGE1
1ST STAGE input pin. Closing this pin will activate the selected Valve. Since the
welding sequence does not start, you can adjust or check the position.
When the 2ND STAGE pin is closed the Weld sequence will be performed.
TB2-2
STAGE2
2ND STAGE input pin. Closing this pin will start the Weld sequence.
TB2-3
WELD CONT
Weld Control pin. Close this pin to turn ON the WELD ON/OFF signal, and open it
to turn it OFF.
Leaving this pin open will shut off welding current even when the sequence
operation is performed. Use this pin, for example, to start the sequence
experimentally.
TB2-4
FLOW SWITCH
Flow switch input pin. Opening this pin will result in a flow rate error.
TB2-5
ERROR RESET
Error/caution reset input pin.
After eliminating the cause of an error or caution, close this pin to reset the error or
caution indication.
20ms or more is required for receiving the input signal.
TB2-6
STEP RESET
Step reset input pin. Closing this pin while the STEPPER is ON will reset the STEP
number to 1.
20ms or more is required for receiving the input signal.