Installing the TSG-3800
TSG-3800 Expansion Shelves
72
TSG-3800 User’s Guide
12778474-002-2 Revision F – March 2004
J9 of 19-inch or J11 of 23-inch (Main Shelf) to J1 (Expansion Shelf) pin connections
are 1 to 1 as are J11 on 19-inch or J13 on 23-inch (Expansion Shelf #1) to J1
(Expansion Shelf #2). Refer to
Table 2-10
for pin assignments. All unlisted pins are
ground connections.
Shelf Alarms
Alarm relays are on the rear of the TSG-3800 Main shelf. Faults that occur on a
module in an expansion shelf are routed back to the CPU module located in the
TSG-3800 Main shelf.
Table 2-10. Pinout for Inter-Shelf Connection
Pin
Function
Description
2
AIF
Ch A Input Fault
4
BIF
Ch B Input Fault
6
OF
Output Fault
8
A/NB
Ch A/Ch B Enabled
12
D4PB
DS1 Ch B Positive
14
D4NB
DS1 Ch B Negative
18
CCPB
Comp Clock Ch B Positive
20
CCNB
Comp Clock Ch B Negative
24
D4PA
DS1 Ch A Positive
26
D4NA
DS1 Ch A Negative
30
CCPA
Comp Clk Ch A Positive
32
CCNA
Comp Clk Ch A Negative
36
CLK1
Clock 1 ‘B’ Signal
38
CLK1
Clock 1 ‘A’ Signal
42
CKFB
Clock Fault ‘B’ Signal
44
CLK2
Clock 2 ‘B’ Signal
46
CLK2
Clock 2 ‘A’ Signal
48
CKFA
Clock Fault ‘A’ Signal
50
FAULT CLR
Fault Clearing Line
Note:
All unlisted pins are ground connections