12778474-002-2 Revision F – March 2004
TSG-3800 User’s Guide 335
System Administrator’s Reference
Provisioning Input Reference Signals
MTIE errors cause an immediate alarm and error message. The error message
displays the time and date of the alarm, the MTIE measurement, and the relevant
time interval.
Displaying MTIE Measurements
To display the most recent 100-second MTIE readings for all inputs, type:
MTIE
then press
Enter
A typical response from the TSG-3800 is:
->MTIE
«date» «time» The MTIE Data (100 sec) for Inp1.1 was 54
«date» «time» The MTIE Data (100 sec) for Inp2.1 was 0
->
To display
n
MTIE measurements for a selected input at a given time interval, type:
MTIE «input» [T100|T1000|T10000] «n»
then press
Enter
where «input» is described in
Table B-3
(default is all inputs)
T100, T1000 and T10000 is the time scale in seconds (default
is T100)
«n» is the number of measurements to display (from 1 to 50;
default is 1).
Example
Purpose: Display the last two 100 second MTIE measurements for the INP3.1
channel.
Command:
MTIE 3.1 T100 2
Display:
TSG->MTIE 3.1 T100 2
«date» «time» The MTIE Data (100 sec) for Inp3.1 was 0
«date» «time» The MTIE Data (100 sec) for Inp3.1 was 0
TSG->
Note:
Recalling a list of the MTIE measurements may not show the
actual reading that exceeds the limit. To view current MTIE data, use
the
STATUS
or
MTIE
command. Specifying a number on the MTIE
command displays stored, completed data.
Note:
Maximum Time Interval Error (MTIE) units are expressed in
nanoseconds (ns).