12778474-002-2 Revision F – March 2004
TSG-3800 User’s Guide 337
System Administrator’s Reference
Provisioning Input Reference Signals
Setting MTIE Limits
To set the MTIE fault limits, type:
MTIE «input» [T100|T1000|T10000] LIMIT [T1|T2] «limit»
then
press
Enter
where «input» is described in
Table B-3
(default is all inputs)
T100, T1000 and T10000 is the time scale in seconds (default
is T100)
T1 is alarm limit 1 and T2 is alarm limit 2
«limit» is the value in ns (maximum 1000000 ns)
Example
Purpose: Set the INP2.1 MTIE limit 1, 100-second interval, to 6000 ns.
Command:
MTIE 2.1 T100 LIMIT L1 6000
Display:
TSG->MTIE 2.1 T100 LIMIT L1 6000
«date» «time» «oper» Set «input» MTIE (100 secs) Limit 1 to
6,000, was 5,022
TSG->
Displaying Frequency Measurements
To display the most recent 100 s, 1,000 s, and 10,000 s interval frequency
measurement for each input, type:
FREQUENCY
then press
Enter
A typical response from the TSG-3800 is:
TSG->FREQUENCY
«date» «time» The Freq Data (100 sec) for Inp1.1 was 70
«date» «time» The Freq Data (100 sec) for Inp2.1 was 0
«date» «time» The Freq Data (100 sec) for Inp3.1 was 0
TSG->
To display
n
frequency measurements for a selected input at a given time interval,
type:
FREQUENCY «input» [T100|T1000|T10000] «n»
then press
Enter
where «input» is described in
Table B-3
(default is all inputs)
T100, T1000 and T10000 is the time scale in seconds (default
is T100)
«n» is the number of measurements to display (1 to 50;
default is 1)
Note:
Frequency units are expressed in picoseconds/second
(ps/sec), where one ps/sec is equivalent to 1 part in 10
–12
.