System Administrator’s Reference
Command Reference
342
TSG-3800 User’s Guide
12778474-002-2 Revision F – March 2004
Clock Command
Use this command to display and provision the Clock module parameters.
Level 0
Not applicable
Level 1
CLK [A|B] [MODE]
CLK [A|B] AR
CLK [A|B] CV
CLK [A|B] TC
where:
A|B selects which clock the command is to affect
Mode displays the current mode: Warmup, Acquire, Locked, Holdover
AR displays the current status of Autoreturn
CV displays the current control value
TC displays the final tau value (time constant)
Level 2
Same as Level 1 operation
Level 3
Same as Level 1 operation, adding:
CLK [A|B] AR [OFF|ON]
CLK [A|B] MODE [WARMUP|ACQUIRE|LOCKED|HOLDOVER]
CLK [A|B] CV [T1|T100][[1-100]|[1-1000]]
CLK [A|B] TC [number|MIN|MAX]
where:
AR sets the AutoReturn mode on the selected clock to On or Off
Mode selects the operating mode:
Warmup = The Clock module is not yet stable
Acquire = The Clock module is syncing with the Input reference signal
Locked = The Clock module is locked to the Input reference signal
Holdover = Input reference signal is invalid
CV sets the control value for the time period of the selected clock
T1 = 1 s average (default); range: 1–100
T100 = 100 s average; range: 1–1000
TC sets the time constant to the specified value or to Min or Max. See
Table B-4
Level 4
Same as Level 3 operation
Remarks
None
Related
Restrictions
None