System Administrator’s Reference
Provisioning Input Reference Signals
332
TSG-3800 User’s Guide
12778474-002-2 Revision F – March 2004
Example
Purpose: Change the OOF error limit from 10 to 15.
Command:
INPUT ALL OOF ERROR 15
Display:
TSG->INPUT ALL OOF ERROR 15
«date» «time» «oper» set OOF error limit to 15, was 10 for
«input»
TSG->
Setting the Clear Limit
The TSG-3800 automatically clears a fault caused by an input error that exceeds its
error limit. This is done by counting the number of consecutive 1-second intervals
that do not contain an error. When the counter exceeds this limit, the alarm clears.
Clearing the alarm resets the error count. The default clear limit is 2. For LOS and
AIS, the clear limit can be set to 1 to 100 seconds. For OOF, BPV and CRC, the
clear limit can be set from 1 to 43200 seconds. Changing this limit affects
all
input
references.
To change the clear limit, type:
INPUT «input» [LOS|CRC|AIS|BPV|OOF] CLEAR «threshold»
then
press
Enter
where «input» is described in
Table B-3
«threshold» is a number from 1 to 43,200
Example
Purpose: Change the OOF clear limit from 2 to 10.
Command:
INPUT 1.1 OOF CLEAR 10
Display:
TSG->INPUT 1.1 OOF CLEAR 10
«date» «time» «oper» set OOF clear limit to 10, was 2 for
«input»
TSG->
Resetting the Error Timer
The operator can reset the input reference error timer to zero for each error type.
Each channel can be reset individually. To reset, type:
INPUT «input» [LOS|CRC|AIS|BPV|OOF] ZERO
and press
Enter
.
where «input» is described in
Table B-3
Example
Purpose: Reset the AIS error timer on the INP4.1 input to zero.
Command: INPUT 4.1 AIS ZERO