12778474-002-2 Revision F – March 2004
TSG-3800 User’s Guide 283
Output Modules
Timing Insertion Module
Configuring the Timing Insertion Module
This section describes how to configure the Timing Insertion module to meet the
requirements of your particular installation.
Overshoot (at 0’ LBO)
10% of peak to base amplitude
Jitter
< 0.03 UI
Drive Capability
0 to 655 feet, 22AWG ABAM cable
Termination Impedance
100
Ω
±
5%
Line Build Out
0-655 ft. in 4 steps
Passive bypass capability
Relay bypasses module on fault
Output on LOS or OOF
AIS or framed all ONEs (switch selectable)
Alarm Conditions
Major Faults
Loss of (or fault in) both clock feeds
Failure of both Clock Modules
Module failure
LOS or OOF on input to TIM
Programmable Faults
SLIP (Major/Minor/Ignored)
Caution:
To prevent ESD damage to the module, always observe the
precautions described in
Properly Handling the Modules
, on page 61.
Table 7-53. Timing Insertion Module Specifications (Continued)
Signal Characteristic
Specification