Special adjustment parameter group 13
PARAMETER DESCRIPTION 293
5.14.3 Vibration inhibition
It is used to suppress the large fluctuation of inverter output current, large fluctuation of motor speed and motor
vibration.
Parameter
Name
Default Setting Range
Content
13-02
P.285
Low frequency
vibration inhibition
factor
5
0~8
If the motor vibrates at a lower frequency, adjust the set
value of 13-02
13-03
P.286
High frequency
vibration inhibition
factor
509
XX00~XX15
00XX~15XX
If the motor vibrates at a higher frequency, adjust the set
value of 13-03. It is recommended to gradually increase the
set value based on the increment of 1
The setting range of the upper two bits and the lower two
bits of 13-03 is 0~15.
Vibration inhibition factor
In practical application, whether the vibration is “low-frequency vibration” or “high-frequency vibration” is usually
determined by the relationship between the occurring vibration frequency and the rated frequency of the motor,
that is:
When the rated frequency of the motor is 50Hz,
If the occurring vibration frequency is lower than 25Hz, it will be deemed as “low-frequency vibration”.
Otherwise, if the occurring vibration frequency is higher than 25Hz, it will be deemed as “high-frequency vibration”.
Note: In case of light load condition, the current fluctuation in a specific operating frequency band may occur in the
motor, which may cause slight vibration of the motor. If the vibration does not affect the application, it can be
ignored.