Analog input and output parameter group 02
PARAMETER DESCRIPTION 131
4mA
20mA
S
e
t
t
i
n
g
f
r
e
q
u
e
n
c
y
02-21
(
P.39)
Input current signal
across terminal 4-5
02-01(P.501) = 1,
frequency command is
selected
02-20(
P.17) = 0
0V
5V
S
e
t
t
i
n
g
f
r
e
q
u
e
n
c
y
02-21
(P.39)
Input voltage signal
across terminal 4-5
0V
10V
02-01(P.501) = 1
frequency command is
selected
02-20(P.17) = 1,2
Note:1. In “external mode” or “mixed mode 2” or “mixed mode 4”, if AU is “on” and 02-01(P.501)=1, target frequency of
inverter is determined by the signal of terminal 4-5; and if AU is “off”, please refer to 02-00(P.500), 02-01(P.501),
02-02(P.504),02-03(P.503).
2. In “external mode” or “mixed mode 2” or “mixed mode 4”, If AU and any one of RH, RM, RL or REX are “on” at
the same time, multi-speed will have the
priority to target frequency.
3. RH, RM, RL, REX, AU mentioned in this paragraph are the functional names of “terminals for multi-function
digital input”. Please refer to 03-00~03-09(P.80~P.84,P.86,P.126~P.128,P.550),03-25~03-30(P.551~P.556),
03-33~03-38(P.559~P.564);
Please refer to section 3.7 for wiring
Terminal 4-5 disconnect function
1)
If 02-24(P.184)=0, after disconnection, inverter will slow down to 0Hz, and after re-connection, the inverter will
accelerate to current given frequency.
2)
If 02-24(P.184)=1, after disconnection, inverter will slow down to 0Hz and at the same time multi-function
digital output terminal will set off an alarm; after re-connection, alarm will be released and the inverter will
accelerate to the current given frequency.
3)
If 02-24(P.184)=2, after disconnection, the keypad will display “AEr” alarm, inverter will stop immediately, and
reset is required to release the alarm.
4)
If 02-24(P.184) = 3, after disconnection, the inverter will continue to run according to the frequency command
before disconnection, the multi-function digital output terminal will set off an alarm, which will be released
after re-connection.
Note:
1.Terminal 4-5 disconnection function is only for current disconnection. Please check the setting of parameter
02-20 (P.17) and the position of SW2.
2.Functional selection of multi-function digital output terminals,
Please refer to
03-10~03-13(P.40,P.85,P.129~P.130),03-42~03-57(P.568~P.583);
Please refer to section 3.7 for wiring
Terminal 4-5 current/voltage input
Terminal 4-5 input current/voltage setting is similar to terminal 2-5. They share same setting except terminal 4-5
doesn’t allow negative voltage and the minimum input current is 4mA.
Note: Functions mentioned above requires flipping the switch SW2 and setting 02-20(P.17).