Basic parameter group 01
PARAMETER DESCRIPTION 112
If 01-22(P.44) ≠ 99999 and 01-25(P.47) ≠ 99999, when RT is “on”, base frequency is the “set value of
01-25(P.47)”.
If 01-43(P.215)=99999, when RT is ON, the base voltage and power voltage are same.
If 01-43(P.215)≠99999, and RT is ON, if the voltage set by 01-43(P.215) is lower than power voltage, the base
voltage is the set value of 01-43(P.215), if the setting voltage value is higher than the power supply voltage, and
the base voltage is power supply voltage.
Note: RT mentioned here is the function name of “multi-function digital input terminal”. Please refer to
03-00~03-09(P.80~P.84,P.86,P.126~P.128,P.550),03-25~03-30(P.551~P.556), 03-33~03-38(P.559~P.564);
Please refer to section 3.7 for wiring
5.2.11 Middle frequency, output voltage of middle frequency
V/F
Parameters can be set when using special motors, especially to adjust motor torque.
Parameter
Name
Default Setting Range
Content
01-26
P.98
Middle frequency 1
3.00Hz
0~650.00Hz
---
01-27
P.99
Output voltage 1 of
middle frequency
10.0%
0~100.0%
---
01-28
P.162
Middle frequency 2
99999
0~650.00Hz
---
99999
Off
01-29
P.163
Output voltage 2 of
middle frequency
0.0%
0~100.0%
---
01-30
P.164
Middle frequency 3
99999
0~650.00Hz
---
99999
Off
01-31
P.165
Output voltage 3 of
middle frequency
0.0%
0~100.0%
---
01-32
P.166
Middle frequency 4
99999
0~650.00Hz
---
99999
Off
01-33
P.167
Output voltage 4 of
middle frequency
0.0%
0~100.0%
---
01-34
P.168
Middle frequency 5
99999
0~650.00Hz
---
99999
Off
01-35
P.169
Output voltage 5 of
middle frequency
0.0%
0~100.0%
---
Middle frequency, output voltage of middle frequency
Please refer to the instructions of 01-12(P.14) =4 in the user manual section 5.2.6 “Suitable load pattern selection
V/F”.
Setting