Appendix 1 Parameter table
APPENDIX 335
Parameter
Number
Group
Name
Setting Range
Default
Page
P.260
06-10
Action when detect over
torque
0: OL2 alarm will not be reported after over torque
detection, and inverter keeps running.
1
1: OL2 alarm will be reported after over torque
detection, and inverter stops.
P.261
06-17
Maintenance alarm function
0: Off
0
1~9998day: Used to set the time for maintenance
alarm output signal
P.262
06-20
Output phase loss protection
0: Off
0
1: When output phase loss, inverter stops and
alarms LF.
P.263
06-07
Decrease carrier protection
setting
0: Fixed carrier frequency, and limit output current
according to carrier value.
0
1: Fixed rated current, and limit carrier according to
output current and temperature.
P.264
10-51
Over excitation deceleration
0: Off.
0
1: Over excitation deceleration is valid.
P.265
10-52
Over excitation current level
0~200.0%
150.0%
P.266
10-53
Over excitation gain
1.00~1.40
1.10
P.267
10-45
Regeneration avoid function
selection
0: Off.
0
1: Regeneration avoid function is always on.
(Automatic calculate Acc/Dec speed )
2: Regeneration avoid function is on only during
constant speed operation (Automatic calculate
Acc/Dec speed )
11:
Regeneration avoid function is always on.
(Manual mode, Acc/Dec speed is set by
10-49(P.271) and 10-50(P.272))
12: Regeneration avoid function is on only during
constant speed operation (Manual mode, Acc/Dec
speed is set by 10-49(P.271) and 10-50(P.272))
P.268
10-46
Regeneration avoid action
voltage level
220V : 155~400V model
380V
440V : 310~800V model
760V
P.269
10-47
Regeneration avoid function
DC bus voltage detection
sensitivity at deceleration
0: Prevent regeneration avoidance from failing
according to bus voltage change rate
0
1~5: Set the sensitivity to detect the bus voltage
change rate. Larger number, higher sensitivity.
P.270
10-48
Regeneration avoid
frequency compensation
value
0~10.00Hz: Set the limit value of regenerative avoid
frequency compensation.
6.00Hz
99999: Off.
P.271
10-49
Regeneration avoid
voltage gain coefficient
0~400.0%/0~40.0%
100.0%
P.272
10-50
Regeneration avoid
frequency gain coefficient
0~400.0%/0~40.0%
100.0%