Protection parameter group 06
PARAMETER DESCRIPTION 189
5.7.5 Over torque detection
Output current detection function can be used for over torque detection.
Parameter
Name
Default Setting Range
Content
06-08
P.155
Over torque detection
level
0.0%
0
Off
0.1~200%
Over torque detection.
06-09
P.156
Over torque detection
time
1.0s
0.1~60.0s
---
06-10
P.260
Action when detect
over torque
1
0
OL2 alarm will not be reported after over torque detection,
and inverter keeps running.
1
OL2 alarm will be reported after over torque detection, and
inverter stops.
Over torque detection
If set value of 06-08
(P.155)
is not zero, over-torque detection function is on.
If output current exceeds over-torque detection level (06-08
(P.155)
) and over-torque detection time (06-09
(P.156)
),
inverter will trigger OL2 alarm and stop. If digital output terminals SO1-SE (03-10
(P.40
)), SO2-SE (03-12(P.129)),
and relays A1-B1-C1 (03-11(P.85)), A2-B2-C2 (03-13(P.130)) are set to over-torque alarm (set value is 19),
inverter will output a signal. If digital output terminals SO1-SE (03-10
(P.40
)), SO2-SE(03-12(P.129)), and relays
A1-B1-C1 (03-11(P.85)), A2-B2-C2 (03-13(P.130)) are set to over-load alarm (set value is 3), and 06-10 (P.260)=1,
inverter will output a signal. Please refer to 5.4.2 Digital output terminals function selection.
100%
06-08
(
P.155
)
output
OL
Reset signal
Output current (%)
Invertor display the OL2 alarm,and the output
stopped,the motor stopped too.
(Overload alarm)
full load current level
time
06-09
(
P.156
)
5.7.6 Stall level when restart
It can set stall prevention level when inverter restart through 06-11(P.160).
Parameter
Name
Default Setting Range
Content
06-11
P.160
Stall level when restart 100.0%
0~150.0%
When restarting, stall prevention operation level.
Stall level when restart
In restart process, if output current of inverter is higher than set value of 06-11 (P.160), inverter will be in a current
stall state.
Setting
Setting
Содержание SA3 Series
Страница 2: ......
Страница 420: ...Appendix 6 European Specification Compatibility Description APPENDIX 418 ...
Страница 421: ...Appendix 6 European Specification Compatibility Description Appendix 419 ...